Advantages |
Optional for lower air flow with large filtering surface applications. |
For laminar flows |
Large filter surface |
Low pressure drop,reduced energy consumption. |
Optimised velocity distribution |
Guaranteed leak-free |
Mechanically stable |
Minimum risk of damage |
One piece, no leak gasket |
<
FILTER CLASS(EN1822) | H11 | H13 | H14 | U15 |
Global Efficiency % for MPPS | ≥95% | ≥99.95% | ≥99.995% | ≥99.9995% |
Local Efficiency % for MPPS | - | 99.75% | 99.98% | 99.9975% |
Recommended Final Pressure Drop | 600Pa | 600Pa | 600Pa | 600Pa |
Max.Final Pressure Drop | 1000Pa | 1000Pa | 1000Pa | 1000Pa |
Continuous Temperature Resistance | 80℃ | 80℃ | 80℃ | 80℃ |
Max.Relative Humidity Resistance | 100% | 100% | 100% | 100% |
Frame | Aluminium | |||
Face Guard | Epoxy painted expanded aluminium grids on both sides | |||
Gasket | One piece foamed polyurethane | |||
Fire Resistance Class | K1/F1 according to DIN53438 | |||
Filter Stage | III | |||
TESTING | Each filter individually tested according to EN 1822 |
<
Efficiency | Width | Height | Depth | Airflow | Pressure Drop | Filtering Surface |
mm | mm | mm | m3/h | Pa | ㎡ | |
H11 | 305 | 305 | 30 | 75 | 70 | 1.3 |
H11 | 457 | 457 | 30 | 170 | 70 | 3.1 |
H11 | 305 | 610 | 30 | 150 | 70 | 2.8 |
H11 | 610 | 610 | 30 | 300 | 70 | 5.5 |
H11 | 610 | 762 | 30 | 400 | 70 | 6.8 |
H11 | 610 | 914 | 30 | 450 | 70 | 8.0 |
H11 | 610 | 1220 | 30 | 600 | 70 | 11.0 |
H13 | 305 | 305 | 30 | 75 | 110 | 1.3 |
H13 | 457 | 457 | 30 | 170 | 110 | 3.1 |
H13 | 305 | 610 | 30 | 150 | 110 | 2.8 |
H13 | 610 | 610 | 30 | 300 | 110 | 5.5 |
H13 | 610 | 762 | 30 | 400 | 110 | 6.8 |
H13 | 610 | 914 | 30 | 450 | 110 | 8.0 |
H13 | 610 | 1220 | 30 | 600 | 110 | 11.0 |
H14 | 305 | 305 | 30 | 75 | 120 | 1.3 |
H14 | 457 | 457 | 30 | 170 | 120 | 3.1 |
H14 | 305 | 610 | 30 | 150 | 120 | 2.8 |
H14 | 610 | 610 | 30 | 300 | 120 | 5.5 |
H14 | 610 | 762 | 30 | 400 | 120 | 6.8 |
H14 | 610 | 914 | 30 | 450 | 120 | 8.0 |
H14 | 610 | 1220 | 30 | 600 | 120 | 11.0 |