Advantages |
Optional for lower air flow with large filtering surface applications. |
For laminar flows |
Large filter surface |
Low pressure drop,reduced energy consumption. |
Optimised velocity distribution |
Guaranteed leak-free |
Mechanically stable |
Minimum risk of damage |
One piece, no leak gasket |
<
FILTER CLASS(EN1822) | H10 | H13 | H14 |
Global Efficiency % for MPPS | ≥95% | ≥99.95% | ≥99.995% |
Local Efficiency % for MPPS | - | 99.75% | 99.98% |
Recommended Final Pressure Drop | 600Pa | 600Pa | 600Pa |
Max.Final Pressure Drop | 1000Pa | 1000Pa | 1000Pa |
Continuous Temperature Resistance | 80℃ | 80℃ | 80℃ |
Max.Relative Humidity Resistance | 100% | 100% | 100% |
Frame | MDF,Galvanized Steel,Stainless Steel | ||
Media | Mini-pleat Glass Fiber Paper | ||
Gasket | One piece foamed polyurethane | ||
Fire Resistance Class | K1/F1 according to DIN53438 | ||
Filter Stage | III | ||
TESTING | Each filter individually tested according to EN 1822 | ||
Optional handle is available |
<
Efficiency | Width | Height | Depth | Airflow |
Pressure Drop |
Filtering Surface |
mm | mm | mm | m3/h | Pa | ㎡ | |
H10 | 305 | 305 | 292 | 450 | 125 | 4.2 |
H10 | 457 | 457 | 292 | 1000 | 125 | 10.0 |
H10 | 305 | 610 | 292 | 900 | 125 | 9.0 |
H10 | 610 | 610 | 292 | 1800 | 125 | 18.0 |
H13 | 305 | 305 | 292 | 450 | 250 | 4.2 |
H13 | 457 | 457 | 292 | 1000 | 250 | 10.0 |
H13 | 305 | 610 | 292 | 900 | 250 | 9.0 |
H13 | 610 | 610 | 292 | 1800 | 250 | 18.0 |
H14 | 305 | 305 | 292 | 450 | 270 | 4.2 |
H14 | 457 | 457 | 292 | 1000 | 270 | 10.0 |
H14 | 305 | 610 | 292 | 900 | 270 | 9.0 |
H14 | 610 | 610 | 292 | 1800 | 270 | 18.0 |